| (1) | These rules and regulations of the Safety Fire Commissioner entitled, "Rules and Regulations for escalators and elevators" are promulgated to establish the State's minimum fire safety codes and standards for escalators and elevators as specified in the Official Code of Georgia Annotated, (O.C.G.A.) Section 8-2-1. |
| (2) | A primary purpose of these rules and regulations is to establish the state minimum safety codes and standards for the prevention of loss of life, injury and structural damage in all buildings, structures and other locations governed by state regulations. |
| (1) | Pursuant to
O.C.G.A. 8-2-1, rules and regulations
adopted by the Safety Fire Commissioner shall have the force and effect of law
and shall have statewide application as being the state minimum fire safety
codes and standards for escalators and elevators and shall not require adoption
by a municipality or county.
|
| (1) | Accident means an unplanned or unscheduled event that results in property damage and/or personal injury. |
| (2) | Act is Part 6 of Article 1 of Chapter 2 of Title 8 of the Official Code of Georgia, O.C.G.A. Sections 8-2-100 through 8-2-109.1. |
| (3) | Approved means that which is acceptable to the Office. |
| (4) | Board is the Advisory Committee as described in Section 8-2-109 of the Act. |
| (5) | Certified Inspector is an inspector, by reason of experience and knowledge, considered qualified by the Office. The minimum experience shall be established by these rules. Knowledge shall be evidenced by approved written and oral examinations, acceptable to and administered by the Office. |
| (6) | Cessation order is the official order stopping an action by an individual or company. |
| (7) | Citation is the written document by which a person or company is summoned or cited. |
| (8) | The Commissioner is the Commissioner of Insurance and Safety Fire, and. |
| (9) | the Office is the Office of the Commissioner of Insurance and Safety Fire. |
| (10) | Dormant Elevator means an elevator that is intact and on the premises and the equipment is entirely disconnected in an approved manner. |
| (11) | Elevators as used in these Rules means, Elevators, Escalators, Dumbwaiters, Material lifts, Manlifts, Moving Walks, or Platform Lifts (Wheelchair Lifts) or Stairway Chairlifts where the Rule is applicable in accordance with the adopted Codes and Standards. |
| (12) | Hand powered one-man elevator is an elevator having a car platform area of not more than five square feet and a rated load of not more than three hundred pounds and which is operated from the car only by pulling on a stationary rope located in the hoistway and passing through or adjacent to the car platform. It is for the exclusive use of certain designated operating and maintenance employees and installed in a grain or feed mill or similar structure not accessible to the general public. |
| (13) | Inspection means the official determination by a certified inspector of the condition of all parts of the equipment meet the applicable code which determines the safe operation of an elevator. |
| (14) | Personnel Hoist is those elevators used during construction to carry workers. Such elevators are temporary and shall not become a permanent part of the structure. |
| (15) | Personal Injury, as used in O.C.G.A. § 8-2-106(a), means bodily injury, sickness, or disease sustained by any person by reason of the operation or malfunction of an elevator, escalator, manlift moving walk or power dumbwaiter, platform lifts or stairway chairlifts including death at any time resulting therefrom. Personal Injury does not include false arrest, detention, imprisonment, confinement, slander, libel, violation of privacy or any mental disease, disability or disorder not accompanied by physical injury at the time of the incident. |
| (16) | Property Damage, as used in O.C.G.A. § 8-2-106(b), means physical injury to, or destruction of tangible property to the structure or operational parts (including safety equipment and devices) of an elevator, escalator, manlift, moving walk or power dumbwaiter, sustained by reason of accident or malfunction, other than routine wear and tear. |
| (17) | Special Purpose Personnel Elevator is an elevator permanently installed to provide vertical transportation of authorized personnel. Such elevators are typically installed in Grain Elevators, Radio Antennas and Bridge Towers. |
| (18) | Deleted for future use. |
| (19) | Temporary Inspection is the inspection by a certified inspector of an elevator to be used on a temporary basis. |
| (20) | Elevator Contractor - Any person, firm, or corporation who possesses an "Elevator Contractor's Certification" in accordance with the provisions of Rule and who is engaged in the business of erecting, constructing, installing, altering, servicing, repairing or maintaining elevators or related conveyance equipment covered by this chapter. |
| (21) | Elevator Mechanic - Any person who possesses an elevator mechanic certification in accordance with the provisions of Rule . |
| (22) | Certification, Elevator Contractor (Class I, Class IR) - A certification issued to an elevator contractor who has proven qualifications and ability, and who has been authorized by the Office to possess this type of Certification. It shall entitle the holder thereof to engage in the business of erecting, constructing, installing, altering, servicing, testing, repairing or maintaining elevators or related conveyance equipment covered by this Chapter. |
| (23) | Certification, Elevator Contractor (Class II) - A certification issued to an elevator contractor who has proven qualifications and ability, and who has been authorized by this Office to possess this type of Certification. It shall entitle the holder thereof to engage in the business of servicing, testing, repairing or maintaining elevators or related conveyance equipment covered by this Chapter. |
| (24) | Certification, Elevator Contractor, Limited (Class III) - A certification issued to an elevator contractor who has proven qualifications and ability, and who has been authorized by the Office to possess this type of Certification. It shall entitle the holder thereof to engage in the business of erecting, constructing, installing, altering, servicing, testing, repairing or maintaining residential dumbwaiters, elevators, platform lifts and stairway chairlifts. |
| (25) | Certification, Elevator Contractor, Limited (Class IIIR) - A certification issued to an elevator contractor who has proven qualifications and ability, and who has been authorized by the Office to possess this type of Certification. It shall entitle the holder thereof to engage in the business of erecting, constructing, installing, altering, servicing, testing, repairing or maintaining residential platform lifts and stairway chairlifts. |
| (26) | Certification, Elevator Mechanic (Class I, Class IR) - A certification issued to a person who has proven qualifications and ability, and who has been authorized by the Office to work on conveyance equipment. It shall entitle the holder to install, service, repair, test, maintain and perform electrical work on elevators or related conveyance equipment covered by this Chapter. |
| (27) | Certification, Elevator Mechanic (Class II) - A certification issued to a person who has proven qualifications and ability, and who has been authorized by the Office to work on conveyance equipment. It shall entitle the holder to service, repair, test and maintain elevators or other conveyance equipment covered in this Chapter. The Class II Mechanic shall be employed by a Class II Elevator Contractor or owner user. |
| (28) | Certification, Elevator Mechanic (Class III) - A certification issued to a person who has proven qualifications and ability, and who has been authorized by the Office to work on residential platform lifts and stair chairlifts. It shall entitle the holder to install, alter, service, repair, test, maintain and perform electrical work on residential elevators, platform lifts and stair chairlifts. |
| (29) | Certification, Elevator Mechanic (Class IIIR) - A certification issued to a person who has proven qualifications and ability, and who has been authorized by the Office to work on residential platform lifts and stair chairlifts. It shall entitle the holder to install, alter, service, repair, test, maintain and perform electrical work on residential elevators, platform lifts and stair chairlifts. |
| (30) | Private Residence - A single unit of a multiple facility or a detached dwelling designed for, inhabited by, and accessible only to one person or that person's family. |
| (31) | LULA Elevator - A passenger elevator limited in size, capacity, travel and speed. These elevators shall comply with ASME A17.1, Section 5.2 (Capacity, Speed, Travel, Etc.) and ICC/ANSI A117.1, Section 407.4 (Car Size, Power Operation, Signal Location, Etc.). |
| (1) | A jurisdiction numbered tag shall be furnished and shall be permanently attached on or near the elevator or dumbwaiters crosshead by the State Deputy Inspector. |
| (2) | On elevators or dumbwaiters without a crosshead, jurisdiction tags shall be attached to the equipment on the car top. Elevators or dumbwaiters without car tops, escalators, manlifts, moving walks or platform lifts (wheelchair lifts) stairway chairlifts, the jurisdiction tag shall be attached on or near the control panel. |
| (1) | All persons inspecting elevator equipment shall be tested for compliance with Georgia statutes and regulations governing escalators and elevators and shall be certified inspectors. |
| (2) | All persons eligible for certification by the Office must have a minimum of three (3) years' experience in the installation, repair, maintenance or inspection of elevators and be a current QEI (Qualified Elevator inspector). |
| (3) | All private inspection firms inspecting elevators in the State of Georgia shall have a minimum of $500,000 general liability insurance issued by a company acceptable to the Office. |
| (4) | All private inspection firms certified by the Office to inspect elevators shall provide the Office of the Insurance and Safety Fire Commissioner a copy of a signed contract for each inspection location and a list of equipment to be inspected. The contract shall give the initial inspection date and expiration date. |
| (5) | Inspection reports shall be sent electronically. Any reports not sent electronically will have a $5.00 entry fee charged per inspection report. |
| (1) | The person, firm or corporation installing, repairing, relocating or altering an elevator shall be responsible for its safe operation, test and maintenance until the elevator is inspected and approved by a certified deputy inspector. |
| (2) | The owner of the equipment shall be responsible for the safe operation and proper maintenance of the elevator. Maintenance records required by the Maintenance Control Program shall be maintained at the location for a period of three (3) years, with the exception of the five (5) year testing, which will be kept for five (5) years. The records shall contain, but not be limited to, all tests, inspections and other maintenance duties referred to in the latest adopted version of ASME A17.1. The records that are kept in electronic format shall also be maintained on site as a printed copy. |
| (3) | The holder of the operating permit shall be responsible for all Code required testing and Code compliance. |
| (4) | The company holding a temporary operating permit shall be responsible for the safe operation and maintenance of the elevator during the period that the temporary operating permit is in force. |
| (5) | All operating permits shall be posted in the elevator car or a sign shall be posted in the car or in the elevator lobby, in a conspicuous location, stating where the permit is located on premises. Operating permits for other equipment shall be posted on or near the control panel or a sign stating where the permit is located. |
| (6) | A Certificate of Inspection shall be conspicuously placed inside each elevator within 72" of the centerline of frame and 72" inches above the elevator cab floor, in a permanently mounted frame with a clear glass or plastic removable cover. The frame shall be sized to provide full visibility of a 2 1/2'' x 3'' certificate. The cover shall be secured by one or more tamper resistant screws. The Inspection Certificate shall be signed and dated for each inspection, by the authorized inspector and replaced at each succeeding inspection. The Inspection Certificate is required in addition to the operating permit. On all other equipment (dumbwaiters, escalators, etc.) the Inspection Certificate shall be placed in a location where it will be visible to the users of the equipment. |
| (7) | All companies performing escalator and moving walk maintenance repair shall have trained personnel and equipment for measuring the "Performance Step Index" on or before January 1, 2003. |
| (8) | An elevator which is inactive for one year, or as removed from service by the owner/user shall be classified as a dormant elevator and placed out of service in accordance with ASME A17.1 Definition Section for "Installation placed out of service." |
| (9) | Before a dormant elevator can be placed in service it shall be inspected by a certified deputy inspector and shall conform to requirements of the applicable standard. |
| (10) | Owners who places elevators in dormant status shall notify the Office within 10 days of the change in status. |
| (11) | Escalators shall not be used as stairs in any location. They will be barricaded with a secure barricade at both the top and bottom landing when temporarily shut down for any reason. |
| (1) | All incidents involving Personal Injury
or Property Damage sustained by reason of the operation or malfunction of an
elevator, escalator, manlift, moving walk or power dumbwaiter, platform lifts
and stairway chairlifts, including death shall be reported by the owner,
operator, lessee, or Maintenance Company as follows:
|
| (2) | Upon receiving a telephonic report or emailed report, the Office may at its discretion determine whether or not to investigate an incident. At the time of the report, the Office shall inform the owner, operator, lessee, maintenance company, or agent reporting the incident whether the Office be investigating and when the elevator, escalator, manlift, moving walk or power dumbwaiter, platform lifts and stairway chairlifts, involved may be repaired or put back in service. In its discretion, the Office may require a telephonic conference with the certified elevator mechanic or Maintenance Company prior to making a decision to investigate an incident. |
| (3) | All telephonic and written reports for accidents involving personal injury shall include the name(s), address, phone number and injuries of the person(s) injured and any witnesses. It will also include a description of the accident. |
The installation of a new, altered, or relocated elevator, escalator, dumbwaiter, material lift, manlift, moving walk, wheelchair lift or chair lift shall not begin until a construction permit has been issued by the authority having jurisdiction for the elevators in the installation area. The equipment shall not be placed into service until it has been inspected, all acceptance tests have been successfully completed in the presence of a certified deputy inspector and all violations have been resolved to the satisfaction of the deputy inspector.
| (1) | An elevator contractor may request a temporary operating permit to allow the use of a passenger or freight elevator before its completion for carrying workmen, authorized personnel or materials. Such elevator shall not be used until it has been inspected and approved by a certified deputy inspector and the required fee has been paid. The operating permit shall be issued for a period not to exceed ninety days. Renewals may be granted at the discretion of the Office, and upon inspection by a certified deputy inspector. |
| (2) | Personnel
Hoist Used During Construction.
|
| (1) | Existing freight elevators shall comply
with the following descriptions:
|
| (1) | Cessation Order.
|
| (2) | Issuance of
Citation or Notice of Administrative Proceeding:
|
| (3) | Hearing Procedure:
|
| (4) | Guidelines for Imposition of Civil
Penalties:
|
| (5) | Minimum recommended penalties.
|
| (1) | A certified inspector may seal an
elevator out of service and void the operating permit if any of the following
conditions exist:
|
| (1) | Payment of required fees and civil penalties imposed under these rules and regulations shall be made in accordance with instructions and forms on the website of the Commissioner of Insurance and Safety Fire. In determining acceptable methods of payment, the Commissioner should consider all relevant factors, including the convenience of the parties, the availability of better means of payment through enhanced technology, the need for efficient administration of the law, and the cost to the agency. |
| (2) | Once permits are processed by this office, no refunds will be issued. |
| (3) | Fees shall be paid in accordance with the
following schedule:
|
| (4) | The Office may provide services or perform inspections not otherwise specified in the fee structure. The charge for this service shall be at the rate of $250.00 per visit, per elevator. |
| (5) | The Office will allow
licensed private inspection companies with valid commissioned inspectors to
perform permit inspections on residential equipment that falls under the scope
of ASME A18.1, latest adopted addition.
|
| (1) | These are the minimum requirements for regular maintenance and safety practices for existing elevators as provided for in the Safety Act and Rules. All existing features or components of the elevator shall comply with the Rules as adopted by the Commissioner. |
| (2) | All existing elevators having a travel of more than 25' 0" shall have "Fire Emergency Service" complying with ASME A17.1 1987 Edition as a minimum. |
| (3) | A permanent decal or metal tag shall be affixed to the lift equipment, in the machine room, control space, machine space, pits, hoistway required to be tested by ASME A17.1, Section 8.6 of the Standard. This decal or tag shall be affixed to the affected equipment when new installations, alterations, or periodic tests are conducted, as required by the Standard. This decal or tag must indicate the date of the test, and the name of the person or firm which performed the test and type of test performed. A decal will not be acceptable when the Standard requires a metal tag. At the time of new installation, alteration, or periodic tests, additional data shall be provided to the building owner or his representative. This document shall include the date of the test, the name of the person or firm conducting the tests and all pertinent data relating to the test. |
| (4) | Mass transit equipment shall have a routine and a periodic inspection as defined by ASME A17.1 latest adopted edition, as modified by O.C.G.A. Section 8-2-102. |
| (5) | Existing Hydraulic Elevators are exempted from the requirements of Rule 8.6.5.8 for five (5) years. Elevators shall have all work required for compliance with ASME A17.3, Section 4.3.3 completed within five (5) years of the effective date of this regulation. Failure to complete work within the required time period will result in the elevator being removed from service until such work is completed, unless the cylinder is replaced. |
| (6) | Existing escalators shall meet the Performance Step Indexing requirements of ASME A17.3, Rule 5.1.11 within two (2) years of the effective date of this Rule revision. |
| (7) | State Elevator Inspectors are not required to meet 8.11, QEI-1 requirements. |
| (8) | Existing passenger elevators shall meet the Restricted Opening of Hoistway Doors or Car Doors as required by ASME A17.3, Rule 2.7.5 within two (2) years of the effective date of this Rule revision. |
| (9) | All existing automatic passenger and freight elevators shall comply with ASME A17.3 Section 3.10.12 within three (3) years of the effective date of this rule. |
| (10) | All elevators shall have emergency key access at all landings that is no greater in height than the applicable code requires. |
| (11) | The data plates required under (d) Section 8.9, Code Data Plate in A17.3 of the latest edition adopted shall follow the requirements of the modifications to 8.9.2 Code Data Plate: "The data plate shall be in plain view, securely attached to each mainline disconnect or controller. It shall also be permitted to locate the data plate in the controller as long as it is in plain view with the controller door open." |
Existing special purpose personnel elevators, and wheelchair lifts shall meet ASME A17.1, the Safety Code for Elevators and Escalators.
All existing belt manlifts shall meet latest adopted version of ASME A90.1 the standards for belt manlifts.
All existing side walk elevators shall meet ASME B20.1, the Safety Standard for Conveyors and related equipment.
All existing dumbwaiters shall meet ASME A17.1, the standards for dumbwaiters.
| (1) | The following sections outline the minimum requirements, regular maintenance and approved safety practices for elevators as provided for in the Georgia Laws Regulating Elevators. All Existing features or components of the elevators shall comply with this law and the rules proposed by the Board and adopted by the Commissioner. |
| (2) | Certified Inspectors shall use the latest adopted edition of the ASME A17.2 inspector's manual with such revision, amendments, and interpretation. |
| (3) | All new elevators machine rooms shall not have sprinklers in these rooms if they are separated from the building with a minimum of a two hour fire separation and have smoke detectors in accordance with NFPA. If these rooms do not have the two hour minimum fire separation they shall have sprinkler protection conforming to the requirements NFPA and shall be provided with means to automatically disconnect the main power supply to the affected elevator prior to the application of water as required by ASME A17.1, unless prohibited by the building code as covered in Section 3007 or 3008. The machine room door shall swing outward from the machine room. Elevator machine rooms must have conditioned air (heated and cooled) to maintain a temperature range between 55 and 90 degrees Fahrenheit, with a maximum relative humidity of 85%. |
| (4) | Elevator machine rooms and machinery
spaces shall be enclosed with fire barriers constructed in accordance with
Section 707 or horizontal assemblies constructed in accordance with Section
711, or both. The fire-resistance rating shall be not less than two hours.
Openings in the fire barriers shall be protected with assemblies having a fire
protection rating not less than that required for the hoistway enclosure doors.
Exceptions:
|
| (5) | All machine rooms, machinery spaces, control rooms, control spaces, and elevator electrical spaces much meet electrical clearances as set in NFPA 70 with the room/spaces access doors closed. This will include all machine rooms, machinery spaces, control rooms, control spaces, and elevator electrical spaces that have fused elevator and cab light disconnects. |
| (6) | All residential elevators will be required to have a machine room, control room, machinery space, or control space with proper electrical clearance as set in NFPA 70 with the door in the closed position with the exception of machine room less elevators that have all equipment located in the hoistway. When the controller is installed outside the hoistway it shall meet the requirements of ASME A17.1 Section 5.3.1.6.2 and NFPA 70, Article 620.71(a), along with all required electrical clearances. |
| (7) | All new elevators shall have a Fireman Emergency Keybox. The keybox is to be a minimum 5.375'' wide by 9'' high by 2'' deep. Front cover shall be hinged on the right side. Lock and key shall be uniform with Lock and Key, Catalogue #25460 or equivalent. Box may either be flush or recessed mounted. Front cover shall be engraved with 1/4'' high letters and shall read in capitals "FIRE DEPARTMENT USE ONLY." Engraving shall be filled with color which will be readily conspicuous. Location of key-box shall be at each bank of elevators in the lobby normally used as a place of entrance to the building. As a minimum, the keybox shall contain the key to the elevator machine room, the elevator hoistway access key, and necessary keys to operate Fireman's Emergency Return System. The key shall be available to Group 1, Group 2 and Group 3 levels of security. This keybox shall be located within sight of the elevator(s) with all required keys at the designated level of Phase I recall. |
| (8) | All new elevators shall be prohibited from providing side emergency exits as detailed in ASME A17.1 Rule 2.14.1.10 provided the elevators are in full compliance with paragraphs (10) and (11) below. |
| (9) | All new elevators shall have the means in the elevator controller for a qualified elevator mechanic to electrically move a stalled elevator to the nearest landing. Key pads or control boxes used for this function shall be permanently installed. |
| (10) | All elevators shall have emergency key access at all landings that is no greater in height than the applicable code requires. |
| (11) | Other Devices - Gravity elevators, hand elevators, incline elevators, multideck elevators, observation elevators, moving walks, material lifts and dumbwaiters with automatic transfer devices and screw column elevators shall meet the requirements of the Codes, as references by these rules. |
| (12) | Reserved for future use. |
| (13) | All new escalators installed after January 1, 2002, shall comply with the latest adopted edition of ASME A17.1. |
| (14) | All variance requests from the law, rules or standards on new, altered or modernized elevator, escalator, dumbwaiter, material lift, manlift, moving walk, wheelchair lift, or stairway chairlift shall be reviewed by the Elevator Advisory Board Members and recommendations given to the Safety Inspection Section. These variance requests shall be submitted to Board Members by Safety Inspection staff for email ballot within three (3) days from the date received. Board Members shall return their votes to approve or disapprove within ten (10) days. The majority of the returned votes are to be considered the recommendation of the Board. |
| (15) | Reserved for future use. |
| (16) | ASME A17.1, Section 5.3 shall be
modified to read as follows:
|
| (17) | 8.9.2 Location: The data plate shall be in plain view, securely attached to each mainline disconnect or controller. It shall also be permitted to locate the data plate in the controller as long as it is in plain view with the controller door open (as modified). |
| (1) | All existing wheelchair lifts and stair lifts installed before January 1, 2002, including temporary installed and portable lifts shall comply with ASME A117.1 and A17.1. |
| (2) | All new wheelchair lifts and stair lifts installed after January 1, 2002, including temporary installed and portable lifts shall comply with ASME A18.1 and A117. If these lifts penetrate a floor, they shall be in a fire rated hoistway and shall comply with Rule . |
| (3) | Residential platform lifts (wheelchair lifts) and stairway chairlifts may be installed and placed into service prior to inspection once the permit and stamped drawings are obtained by the installation company. The installation and testing shall be done to the requirements of ASME A18.1, the latest adopted version. The installation and testing will be done by a Class IIIR elevator mechanic and a test report signed by them showing that both the installation and all tests required in Section 10 of the Code have been completed. A copy of the permit will be posted at the location and a copy of the test report will be emailed to safety engineering. The permit inspection, to include all testing will be conducted as soon as possible after the installation by a certified elevator mechanic of the company that installed the equipment. |
| (1) | Elevator Contractor (Class I): Any persons, firms, partnerships, corporations or companies wishing to engage in the business of installation, alteration, service, replacement or maintenance of elevators, dumbwaiters, escalators, moving walks, residential elevators, platform lifts, and/or stairway chairlifts shall apply for Certification by the Office on a form provided by the Office. They shall receive Certification prior to permitting any work or engaging in any business activity. |
| (2) | Elevator Contractor (Class IR): Any persons, firms, partnerships, corporations or companies wishing to engage in the business of installation, alteration, service, replacement or maintenance of ASME A17.1, Section 4 and 5.7 elevators, temporary construction elevator and material lifts or separately cab interiors and phones, shall apply for Certification by the Office on a form provided by the Office. They shall receive Certification prior to permitting any work or engaging in any business activity. |
| (3) | Elevator Contractor (Class II): Any persons, firms, partnerships, corporations or companies wishing to engage in the business of alteration, service, replacement or maintenance of elevators, dumbwaiters, escalators, moving walks, residential elevators, platform lifts, and/or stairway chairlifts shall apply for Certification by the Office on a form provided by the Office. They shall receive Certification prior to permitting any work or engaging in any business activity. |
| (4) | Elevator Contractor (Class III): Any persons, firms, partnerships, corporations or companies wishing to engage in the business of installation, alteration, service, replacement or maintenance of residential dumbwaiters, elevators, platform lifts, and/or stairway chairlifts shall apply for Certification by the Office on a form provided by the Office. They shall receive Certification prior to permitting any work or engaging in any business activity. |
| (5) | Elevator Contractor (Class IIIR): Any persons, firms, partnerships, corporations or companies wishing to engage in the business of installation, alteration, service, replacement or maintenance of residential platform lifts, and/or stairway chairlifts shall apply for Certification by the Office a form provided by the Office. They shall receive Certification prior to permitting any work or engaging in any business activity. |
| (6) | Elevator Contractor's Certification shall expire twelve (12) months following the date of issuance after April 1, 2014. |
| (7) |
Qualifications of Elevator Contractor.
|
| (8) | The application for Elevator Contractor
Certification shall contain the following information:
|
| (9) |
The application for Elevator Mechanic shall contain the following information:
|
| (10) | All elevator mechanics installing, altering, repairing, maintaining, or servicing elevators, escalators, moving walks, dumbwaiters, material lifts, residential elevators, platform (wheelchair) lifts and stairway chairlifts after January 1, 2006 shall have a "Certificate of Authorization" issued by the Office. |
| (11) | Approval of training programs for Certification and Recertification of elevator mechanics. The Elevator Advisory Board shall review and approve all certification and recertification programs. The Office of Insurance and Safety Fire Commissioner shall prepare a testing program. |
| (12) | Renewal applications. Applicants
renewing their Certification shall provide the following information:
|
| (13) |
Qualification of Class I Elevator Mechanic.
|
| (14) | Qualification of
Class IR Elevator Mechanic.
|
| (15) | Qualification for Class II Elevator
Mechanic.
|
| (16) | Qualification for Class III Elevator
Mechanic.
|
| (17) | Qualification for Class IIIR Elevator
Mechanic.
|
| (18) | Issuance and Renewal of Certification.
|
| (19) | Suspension and Revocation of
Certification.
|
| (1) | Class I, Class IR and Class II Elevator Contractors shall submit to the Office an original or certified copy of an insurance policy issued by an insurance company authorized to do business in this State to provide general liability coverage of at least one million dollars ($1,000,000.00) for injury or death of one person and one million dollars ($1,000,000.00) for injury or death of any number of persons in any one (1) occurrence, with the coverage of at least five hundred thousand dollars ($500,000.00) for property damage in any one (1) occurrence and the statutory workers compensation insurance coverage. |
| (2) | Class III and IIIR Elevator Contractors shall submit to the Office an original or certified copy of an insurance policy issued by an insurance company authorized to do business in this State to provide general liability coverage of at least five hundred thousand dollars ($500,000.00) for injury or death of one (1) person and at least five hundred thousand dollars ($500,000.00) for injury or death of any number of persons in any one (1) occurrence, with the coverage of at least two hundred fifty thousand dollars ($250,000.00) for property damage in any one (1) occurrence and the statutory workers compensation insurance coverage. |
| (3) | Private Elevator Inspectors shall submit to the Office an original or certified copy of an insurance policy issued by an insurance company authorized to do business in this State to provide Professional Errors and Omissions Insurance coverage of at least one million dollars ($1,000,000.00) for injury or death of one person and one million dollars ($1,000,000.00) for injury or death of any number of persons in any one (1) occurrence, with the coverage of at least five hundred thousand dollars ($500,000.00) for property damage in any one (1) occurrence and the statutory workers compensation insurance coverage. |
| (4) | Such policies must be issued by an insurance company authorized to do business in the State of Georgia by the Insurance Commissioner with a Best Policyholders rating of "A-" or better and with a financial size rating of Class V or larger. |